TIA and ISO standards provide one additional step for the grounding of screened and shield cabling systems. Specifically, clause 4.6 of ANSI/TIA–B.1 and clause 11.3 of ISO/IEC 11801:2002 state that the cable shield shall be bonded to the TGB in the telecommunications room, and that grounding at the work area may be accomplished through the equipment power connection. This procedure is intended to support the optimum configuration of one ground connection to minimise the appearance of ground loops, but recognises that multiple ground connections may be present along the cabling. Since the possibility that grounding at the work area through the equipment may occur was allowed for within ANSI–J–STD–A, there is no need to avoid specifically grounding the screened/shielded system at the end user's PC or device.
Если электрика по стандарту, да еще по буржуйскому с изолированной нейтралью, то да, можно и правильно хоть в каждой точке землить. Я про наши реалии. В которых да, полностью согласен, кидаем волокно и забываем это всё это заземление с экранированием как страшный сон.. по питанию только вопросы остаются. Ну, и еще если волокно в броне или с тросом, по ним тоже бывает.. было, 0.4 удачно уронилась на ВОК с тросом и расплавила на фиг метров 400. Так что лучше диэлектрик..